7/30/01
2
32F° - 113 F° (0 C° - 45 C°)
Specified Temperature Range
Backlit alphanumeric LCD displays - AC amps, AC voltsrms, DC volts, AC frequency, output power (W) and (Wh) produced.
User Display
Over/under AC Voltage and frequency detection plus active islanding detection - Meets IEEE 929 and UL 1741 requirements.
Islanding Protection
Single Pole 100 amp DC rated circuit breaker.
DC Disconnect
Double pole 15 Amp 240 VAC branch circuited rated breaker.
AC Disconnect
Less than 5% at rated power per IEEE 929 and UL 1741
Total Harmonic Distortion
Sine wave, high frequency PWM controlled
AC Output Waveform
59.5 - 60.5 Hz. Default
Frequency Window - Min/Max
60 Hz
Nominal Frequency -
Current source
AC output characteristics
211 - 254 VAC
AC Voltage - Min/Max
94%
Efficiency Peak
125 VDC
Absolute Maximum PV Open Circuit Voltage
50 VDC
Minimum Wake-up DC Input Voltage
52 VDC (typically, four nominal 12 VDC PV modules, in series)
Minimum Input DC voltage (for full rated AC output)
42 - 85 VDC
Maximum Power point tracking voltage range
240 VAC
AC Voltage - Nominal